If You Still Think KEPCO's Power Factor Threshold Is 90%, It Changed

Key summary

KEPCO's reference power factor isn't 90% — it's 92% lagging during daytime hours and 95% leading at night. For every 1 percentage point off the reference, the basic charge is adjusted by 0.2%; the discount is capped at 1.0%, but the surcharge can run as high as 7.0%. Based on Articles 42 and 43 of the Basic Terms of Supply, this piece covers the calculation method and the risk of capacitor overcompensation.

Electricity costs · August 28, 2026 · 6 min read

Contents (8)

Power factor is the quietest line on the bill. The amount does not look large and nobody explains it, so many plants let it pass for years. Yet this line is applied as a percentage of the whole basic charge, so the bigger a plant's basic charge, the bigger the cost of leaving it alone.

What is power factor?

Power factor is the share of the electricity arriving at your plant that actually does work. It is active power divided by apparent power, and it is usually written as a percentage.

Equipment with coils in it — motors, welders, transformers — creates and collapses magnetic fields, and in doing so produces a share that never turns into work: reactive power. The larger that share, the lower the power factor.

Why does a low power factor mean paying more?

Because when reactive power grows, KEPCO has to provide heavier equipment to get the same work done. So KEPCO adjusts power factor directly through the tariff.

Under Article 43(1) of the Terms, the power factor charge applies to customers with a meter installed that can measure reactive power, and who is covered depends on the voltage.

Contract types the power factor charge applies to (Basic Terms of Supply, Article 43(1))

  • Low-voltage (item 1) — General, Industrial, Agricultural and Temporary Service with contract power of 20kW or more
  • High-voltage and above (item 2) — General, Educational, Industrial, Agricultural and Temporary Service
Educational Service exists only at high voltage and above — there is no power factor charge on low-voltage Educational Service

Where it lands matters too — it is added to or taken off the basic charge as a percentage, not the energy charge, so you need to know how the basic charge is calculated to gauge the size of it.

Two transmission towers standing against a sky at dusk. Insulators and conductors run between them.
The more reactive power grows, the heavier the lines and the larger the transformers KEPCO has to provide to get the same work done. The power factor charge is the device that returns the cost of that provision through the tariff. Photo: Unsplash free licence

Is the reference power factor 90% or 92%?

It is 92%. The widely circulated "90% power factor reference" does not match the current Terms. Article 43(2) of the Basic Terms of Supply in force from 1 February 2025 sets the daytime lagging power factor reference at 92% and the night-time leading power factor reference at 95%.

Material that says "lagging 09:00~23:00 / leading 23:00~09:00" is from a version before the amendment.

ItemHours it appliesReference power factorDirection of adjustment
Lagging power factor08:00~22:0092%Above it, a reduction; below it, a surcharge
Leading power factor22:00~08:00 the next day95%Below it, a surcharge only. No reduction

Measurement is done in 30-minute intervals (Article 42(2) of the Terms). These 30-minute values are averaged over the month to set the charge, but caps and floors are applied before the average is taken.

On the lagging side, anything below 60% is treated as 60% and anything above 97% as 97% (Article 43(2), item 1(b)); on the leading side, anything below 60% is treated as 60% and intervals that are in fact lagging are treated as 100% (Article 43(2), item 2(b)).

Customers supplied at low voltage and customers without remote metering have their power factor calculated not from 30-minute intervals but from the value accumulated on the meter over one month (the proviso to Article 42(2)).

The two groups are separate — if you are on low voltage you fall here regardless of whether you have remote metering.

How much is the power factor charge?

0.2% of the basic charge for each percentage point away from the reference. The unit step is the same for the surcharge and for the reduction.

A worked example — a plant whose basic charge is KRW 3 million a month, taken as an assumption.

Daytime average power factorDifference from the reference (92%)Adjustment rateMonthly adjustment (example)
97%+5%p1.0% of the basic charge taken offKRW 30,000 reduction
82%−10%p2.0% of the basic charge addedKRW 60,000 surcharge
70%−22%p4.4% of the basic charge addedKRW 132,000 surcharge

When an additional charge arises, the first month is only a notice of the charge to come and it is actually billed from the second month (Article 43(3) of the Terms). If a notice has appeared on your bill, that means you have a month's grace.

Which is larger, the discount or the surcharge?

The surcharge is far larger. At the extremes the difference is close to sevenfold. The reduction stops at 97%, while the surcharge runs all the way down to 60%.

Maximum adjustment against the basic charge (a direct consequence of the text of Article 43(2) of the Terms)

Maximum reduction, lagging power factor (92→97%)1%
Maximum surcharge, lagging power factor (92→60%)6.4%
Maximum surcharge, leading power factor (95→60%)7%

So describing power factor improvement as "going to collect a discount" makes people misjudge the size of it. Strictly, it is about stopping a fine you have been paying, and the 1.0% reduction is a bonus that follows afterwards.

Why is night-time power factor treated separately?

Because at night the load falls away while the capacitors stay connected, so the power factor crosses over to the other side. That state is leading power factor, and it carries a surcharge with no reduction (Article 43(2), item 2 of the Terms).

However, the leading power factor charge does not apply to customers supplied at low voltage or to customers without remote metering (Article 43(2), item 2(c) of the Terms — the customers covered by the proviso to Article 42(2)).

If you are on low voltage there is no night-time leading surcharge whether you have remote metering or not. So the night-time leading problem is in practice a problem for plants at high voltage and above.

Where do we check our plant's power factor?

On the power factor lines of the monthly electricity bill, and in the usage data KEPCO provides. The power factor charge is billed as an addition to or reduction of the basic charge, so start by looking for the surcharge or reduction entry in the billing detail.

To see the values at 30-minute resolution you have to obtain the data from KEPCO yourself. The route for that is set out in how to obtain KEPCO usage data.

You have to look at day and night separately to tell whether the problem is on the lagging or the leading side.

Does fitting capacitors always make things better?

No. Fit too many and the loss grows. Put in generous capacity to fix the daytime lagging power factor and, at night when the load drops away, it crosses over into leading power factor, and you pay several times the reduction cap of 1.0% as a surcharge.

On top of that, ending up with a leading power factor because capacitors beyond the appropriate capacity have been installed is a ground for suspension of supply under the Terms (Article 45(3), item 8 and Article 41 of the Terms).

What to check before touching power factor

  • Look at the average power factor for day (08:00~22:00) and night (22:00~08:00) separately — the prescription is the exact opposite
  • If you are supplied at low voltage, the night-time leading surcharge does not apply to you in the first place, whether or not you have remote metering
  • Sizing capacitor capacity and automatic power factor controllers is the licensed electrical safety manager’s territory. Settle the capacity first, then get quotes
  • After installation, check again with a month of 30-minute data whether you have gone leading at night
The first month is a notice, the billing starts from the second. If you act in the month the notice appears, you can avoid the actual charge.

Some outfits sell power factor correction equipment as "a device that cuts your electricity bill by 20%", but as the tables above show, the money that moves with power factor is a few per cent of the basic charge.

We worked that arithmetic through further in do power-saving devices work, and it is worth reading alongside the point that power factor is one line among several in the structure of the industrial electricity tariff.

  • [Source: KEPCO Basic Terms of Supply, Article 43 (additional charge or reduction according to power factor), in force 2025.02.01]
  • [Source: KEPCO Basic Terms of Supply, Article 42 (calculation of power factor), in force 2025.02.01]
  • [Source: KEPCO Basic Terms of Supply, Article 41 (maintenance of power factor) · Article 45 (suspension of supply for reasons attributable to the customer), in force 2026.07.01]

Note: The monthly adjustments in this piece are examples assuming a basic charge of KRW 3 million. The actual amounts vary with the contract type and the billing demand, and sizing capacitor capacity is a matter for the judgement of a licensed electrical safety manager.

OpenEnergy Editorial Team

Electricity costs

We unpack KEPCO tariff structure and cost-cutting methods in practical terms.

More on Electricity costs →

Talk to an expert about your company's K-RE100 transition

Tell us about your situation and someone here will write back with the right transition route.

We use these details only to answer this enquiry.