Contract Power: Why Your Plant Was Given That Number

Key summary

Contract power isn't actual usage — it's a value set in advance from a factory's equipment capacity. This piece covers how the conversion-rate calculation in Article 20 of KEPCO's Basic Terms of Supply works, how to check it, and how contract power drives up the basic charge every month.

Electricity costs · August 24, 2026 · 6 min read

Contents (8)

Seeing a figure like "contract power 300kW" at the top of the bill, it is easy to think it means your plant uses that much. It does not. Contract power is not the amount you used but the capacity held ready for you to use, and the cost of holding it ready is billed to you every month as the basic charge.

What is contract power?

Contract power is the capacity of electricity (kW) a customer has agreed to receive from KEPCO. Regardless of how much you actually used, it is the reference figure against which KEPCO prepares equipment such as transformers and lines so that it can supply that capacity at any time. The cost of that preparation is what is billed at a fixed level every month as the basic charge.

In other words, contract power is not a record of consumption but a promise. If you do not run a single machine this month, your contract power is unchanged, and so is the basic charge that follows from it.

Who sets contract power, and how?

The way contract power is set is laid down in Article 19 (criteria for determining contract power) and Article 20 (method of calculating contract power) of KEPCO's Basic Terms of Supply, and in Articles 11 and 12 of the Implementation Rules (KEPCO's official website, "criteria for calculating contract power", consulted September 2026). It is not a figure set at will but the result of a formula laid down in the Terms.

There are two broad bases for the calculation.

Basis of calculationHow contract power is setAuthority
Contract power based on connected equipmentThe sum of the individual input ratings of the connected equipment × the contract power conversion rateBasic Terms of Supply, Article 20(1)
Contract power based on transformer equipmentThe sum of the rated capacities of the primary transformers (1kVA is treated as 1kW)Basic Terms of Supply, Article 20(2)

Where a piece of equipment's capacity is shown as both input and output, the input shown is the figure applied. Even if a large output figure in kW is printed on the motor nameplate, the figure that goes into the contract power calculation is the input.

Does adding up all the equipment capacity give you contract power?

No. When the calculation is done on the connected equipment basis, conversion rates that step down by band are applied to the total. The tariff structure already reflects the fact that not all of a plant's equipment runs flat out at once.

Band of total connected equipmentContract power conversion rate
First 75kW100%
Next 75kW85%
Next 75kW75%
Next 75kW65%
The part above 300kW60%

(KEPCO Basic Terms of Supply, Article 20(1), as published on KEPCO's official website in September 2026)

A worked example. For a plant whose connected equipment totals exactly 300kW, contract power comes out like this.

75 × 100% + 75 × 85% + 75 × 75% + 75 × 65% = 243.75kW → 244kW

You installed 300kW of equipment, and your contract power is 244kW. The Terms provide that where the total of the calculation has a remainder of less than 1kW it is rounded at the first decimal place, so 243.75kW becomes 244kW.

This example is calculated using the conversion rates above alone; actual contract power varies with the equipment configuration and with whether the transformer basis is applied.

Why do contract power and actual consumption differ?

Because contract power comes from equipment capacity, while actual consumption comes from what you ran, and for how many hours, on the day. There is no reason for the two figures to agree in the first place.

At one low-voltage site we observed through our own SaaS, the measured maximum load at 15-minute resolution was 36kW, while the power used in the charge calculation on the KEPCO bill was the contract power of 50kW (July 2026, from observation of our own production data). In effect the site paid a basic charge every month on 14kW of capacity it had never actually used.

The second figure that creates this gap is maximum demand, and which of the two becomes the basis of the charge is settled in the difference between contract power and maximum demand.

Transmission towers in a line against a red sky at dusk. The sun has settled near the horizon and conductors run between the towers.
The towers stand in a line not to match ordinary consumption but to match the moment of the heaviest draw. Contract power rests on the same premise. Photo: Unsplash free licence

What is the loss if contract power is too high?

You end up paying a basic charge every month on capacity you have not used. The basic charge is worked out by multiplying the billing demand by a unit price rather than by consumption, and contract power is what holds that billing demand up.

Article 68 of KEPCO's Basic Terms of Supply splits customers into two paths.

  • Customers covered by Article 68(2): the billing demand is the contract power as it stands. If contract power is excessive, that excess is a straight loss.
  • Customers covered by Article 68(1): the billing demand is set from maximum demand, but where that value is less than 30% of contract power, 30% of contract power is applied. In other words, however little you use, 30% of contract power is laid down as a floor.

(Basic Terms of Supply, Article 68, in force 1 July 2026)

So if contract power is excessive, a loss arises for either kind of customer, and it repeats every month. The order in which the basic charge itself is calculated is set out separately in how the basic charge is calculated.

What happens if contract power is too low?

Use more than your contract power and an excess-use surcharge is applied. Article 67-3 of KEPCO's Basic Terms of Supply and Article 48-2 of the Implementation Rules (in force 1 July 2026) provide that where contract power is exceeded, a surcharge is levied at the basic charge unit price multiplied by a factor. The first month in excess is only a notice, however, and it is actually billed from the second month.

The point to watch is that the axis on which the surcharge is judged differs by customer group (Basic Terms of Supply, Article 67-3).

The excess-use surcharge — the axis of judgement by customer group

Covered by Article 68(1) (high voltage and similar)

Basis of judgement
By how much it was exceeded — the excess ratio
Factor
150~400%

Low voltage, contract power 20kW or more with a meter installed

Basis of judgement
How many times it was exceeded — the number of occurrences
Factor
150~250%

So contract power means a monthly loss if it is too high, and a surcharge risk if it is too low. That is why a reduction has to be decided only after working out how much headroom to leave, and that calculation and the application procedure are covered in the procedure for changing (reducing) contract power.

Where do we check our plant's contract power?

In three places, and all three should show the same figure.

Roadmap · Where to check contract power

  1. 1

    STEP 1

    The electricity bill

    The contract type and contract power lines

  2. 2

    STEP 2

    KEPCO Cyber Branch

    Look up the contract details with your customer number

  3. 3

    STEP 3

    The electricity supply contract

    The original document from when the contract was signed

If the three figures differ, it may be that a contract change following the addition or scrapping of equipment was never reflected. How to obtain your usage data at the same time is set out in how to obtain your plant's electricity usage data from KEPCO.

How do we judge whether contract power is right?

You cannot judge it from contract power alone. You have to set it side by side with the record of maximum demand over the last 12 months. If the actual maximum load keeps forming well below contract power, that is a signal that the capacity is excessive; conversely, if the maximum load sits right up against contract power, there is no room to reduce it.

A checklist for reviewing contract power

  • Has maximum demand over the last 12 months ever gone above half of contract power?
  • Is equipment that has been scrapped or is not in use still left in the contract power calculation?
  • Did you change the contract after adding equipment, but the contract power on the bill stayed the same?
  • Do you know whether it was worked out on the transformer basis or the connected equipment basis?
If the answer to 1 is no and the answers to 2 and 3 are yes, you are a candidate for reviewing contract power

That said, reducing contract power is not an easy decision to reverse, so we would recommend securing the data the judgement rests on first and then going through the procedure for changing (reducing) contract power. Contract power also decides whether your plant falls under Industrial (A) or Industrial (B) — it is worth reading the difference between Industrial (A) and Industrial (B) alongside this.

Note: The conversion rates and article numbers are as published on KEPCO's official website in September 2026. The Terms may be amended, so please check the latest version before entering into an actual contract. The calculations in this piece are examples.

OpenEnergy Editorial Team

Electricity costs

We unpack KEPCO tariff structure and cost-cutting methods in practical terms.

More on Electricity costs →

Talk to an expert about your company's K-RE100 transition

Tell us about your situation and someone here will write back with the right transition route.

We use these details only to answer this enquiry.